| Unit Parameter Table | |||
| Air-cooled Module Unit Parameter Table | |||
| Unit Type Unit parameters |
ZGR-65ⅡAG2 | ZGR-130ⅡAG2 | |
| Rated Refrigeration (A35/W7℃) |
Cooling Capacity(kW) | 65 | 130 |
| Power(kW) | 20.3 | 40.6 | |
| EER | 3.20 | 3.20 | |
| Rated Heating (A7/W45℃) |
Heating Capacity(kW) | 70 | 140 |
| Power(kW) | 20.5 | 41.0 | |
| COP | 3.41 | 3.41 | |
| Mains | 380V/3N~/50Hz | ||
| Maximum Operating Current(A) | 58 | 115 | |
| Cooling Operating Ambient Temperature Range(℃) | 16~49 | ||
| Heating Operating Ambient Temperature Range(℃) | -15~28 | ||
| Cooling Water Temperature(℃) | 5~25 | ||
| Heating Water Temperature(℃) | 30~50 | ||
| Refrigerant | R410A | ||
| Safeguard | Higher-lower voltage protection, antifreeze protection, overload, water flow protection, etc. | ||
| Capacity Adjustment Method | 0~100% | 0~50%~100% | |
| Throttling Method | Electronic Expansion Valve | ||
| Water Side Heat Exchanger | Shell and Tube Heat Exchanger | ||
| Wind Side Heat Exchanger | High-efficiency Finned Tube Heat Exchanger | ||
| Fan | High Efficiency and Low Noise Axial Flow Fan | ||
| Water System | Chilled Water Flow(m³/h) | 11.2 | 22.4 |
| Hydraulic Pressure Drop(kpa) | 40 | 75 | |
| Maximum Working Pressure(Mpa) | 1.0 | ||
| Water Pipe Connection | DN65(Flange) | DN80(Flange) | |
| Anti-shock Protection Type | Ⅰ | ||
| Waterproof Level | IPX4 | ||
| Dimentions | Length(mm) | 1930 | 2340 |
| Width(mm) | 941 | 1500 | |
| Height(mm) | 2135 | 2350 | |
| Weight(kg) | 590 | 1000 | |
| Rated refrigeration: outdoor dry/wet bulb temperature is 35°C/24°C; outlet water temperature: 7°C | |||
| Rated heating: outdoor dry/wet bulb temperature is 7℃/6℃; outlet water temperature is: 45℃ | |||
| Models, parameters, and performance will be changed due to product improvements. Please refer to the actual product and nameplate for specific parameters; | |||
| Executive Standard:GB/T 18430.1(2)-2007 GB/T 25127.1(2)-2010 | |||